Inner Range

The LAN Power Supply is a dual 2A supervised power supply producing 4A nominally split evenly between system power and dedicated battery charging.

Up to three additional LAN Power Supplies can be slaved to one LAN Power Supply. Each slave can be configured ifferently to tailor power output to system requirements.

Ganged LAN Power Supplies come into their own in installations where express charging of large back up battery banks is needed.

The LAN Power Supply connects to the Concept system LAN, communicating status of the supply and is applicable where battery backed 12V supplies are required to power other unpowered Inner Range modules, detectors, readers and auxiliary devices such as strobes, sounders, locks, etc.

Features:

  • Dual 2A power supply (2A system power + 2A battery charging)
  • Up to 4 units can be linked in a master / slave layout to provide 14A dedicated for charging or detector power. Slaves can be configured as:
    • Split (2A power / 2A charging)
    • Charger only
    • Power only
    • Spare
  • Reports status of fault, tamper plus input and output conditions to Control Module through Concept LAN
  • Contains 2 general purpose zone inputs
  • Additional switched 12V output auxiliary with current monitoring for use with satellite sirens
  • 12V auxiliary can be used as 12V power source for strobes, 12V lamps when current monitoring switched off

Download data sheet

 
 
  • Dual 2A power supply for system power and dedicated battery charging
  • Perfect for rapid charging of large battery back up systems
  • Up to 4 units can be linked in master / slave configuration producing a minimum 14A for battery charging
 
Physical  
Cabinet Dimensions 325(L) x 250(W) x 112(D) (mm)
PCB Dimensions 200(L) x 95(W) x 40(D) (mm)
Installation Environment 0° – 40°C @ 15% to 85% Relative humidity (non-condensing)
Weight 8kg (including mains transformer, battery and cover)
Electrical   PCB Versions    Transformer Versions
Mains Input Voltage N/A 240VAC, 50Hz
Mains Input Current N/A 500mA
Input Voltage to PCB 16-18VAC 16-18VAC
Fuse Protection Separate fuses for Battery , Siren 1, Siren 2, LAN & Detector Power
Current Consumption  
Total Current Limit 4A 4A
Recommended allowance for battery charging   2A*   2A*
Available Current (for relays, detectors, auxiliaries , etc.)   2A*   2A*
  *Slaved LAN Power Supply units can be configured to deliver 4A of battery charging current but no detector power or vice-versa.
Power Supply Output  
Output Voltage 13.75VDC +/-2% up to 4A
Maximum Output Current 4A (combined current from DET+, LAN+, BAT+ and auxiliaries)
Output Ripple 100mV RMS maximum @ Iout=2A
Switching Frequency ~50kHz
Load Regulation +/-100mV @ Iout=0.1A to 4A
Conversion Efficiency ~80%
Battery  
Battery Capacity (per 2A supply) 12V 7Ah Sealed Lead Acid Battery (no slaves connected)
Battery Input Fuse 5A
Output Protection  
DET+ Fuse 5A
LAN+ Fuse 5A
AUX2 Fuse 5A