Inner Range


The Control Module is the heart of the Concept 4000 hardware platform. This unit integrates access control, security management and building automation features.

The Control Module comes with 16 zone inputs, 2 outputs, an on board switch mode power supply, LAN port, modem, serial port, siren and relay outputs.

For a full range of system features delivered by the Concept control module, please see the Concept Features Summary page.

Download Control Module data sheet

Control Module ordering and memory upgrades

Concept 4000 Control Module 32K 995001
Concept 4000 Control Module 128K 995002
     
128K Memory Upgrade Chip 128K 995015
512K Memory Upgrade Chip 512K 995016
32K Memory Replacement chips 32K

995017

Options Chips
Additional advanced functionality such as programmable site codes, high level lift interfaces etc. can be enabled with the purchase of special options chips. Please consult your distributor for ordering details.

Expansion options

  • 8 Relay expander board
  • 8 auxiliary output expander board
  • 1-4 port RS232/Ethernet

Download Control Module Options data sheet

 
 
  • A flexible platform that can accommodate
    projects from a domestic installation right
    up to a multi-faceted high-rise building
    management system.
  • Unlimited system dimensions when combined with Insight software
  • A single control module starts at a cost effective entry point and , can scale up to 50,000 users, 250 modules, 250 doors, 250 areas
  • Memory Configurations are used to optimise system dimensions based on specific project requirements
 

 

 

Connectivity

The control module is the heart of a Concept 4000 system.

 

 

 


 

Physical  
Cabinet Dimensions 460(L) x 358(W) x 85(D) (mm)
PCB Dimensions 200(L) x 200(W) x 45(D) (mm) (Inc. Heat sink)
Weight 9.5Kg (in Medium Low Profile Enclosure)
Installation Environment 0°C - 40°C @15 - 85% Relative humidity (non-condensing)
Cabinet Battery Bracket To suit 12V 7AH Sealed Lead Acid battery
Electrical    Plugpack Versions    Transformer Versions
Mains Input Voltage 240VAC, 50Hz 240VAC, 50Hz
Mains Input Current 100mA 500mA
Input Voltage to PCB 16-18VAC 16-18VAC
Fuse Protection Separate fuses for Battery , Siren 1, Siren 2, LAN & Detector Power
Current Consumption  
Total Current Limit 1.3A 2.2A
Operational Current
(No peripherals connected)
  275mA   275mA
Recommended allowance for battery charging   300mA   300mA
Available Current (for relays, detectors, auxiliaries , etc.)   700mA   1.2A
Inputs  
Zone Inputs 16
Cabinet Tamper Input Yes
Outputs  
Siren Outputs 2 (Internal & External) Max Load: 2 x 8 Ohm, 10 Watt siren speakers
Outputs (open collector) 2 (Expandable to 10 using the 8 Auxiliary Expander board-995055)
Relays Expandable to 8 with optional Passive Relay board-995084 - replaces Auxiliaries 3-10